CommissioningThe units are factory pre-set and commissioned and should not need any field adjustment. However, if after aperiod of time the unit is f
PS1061-C-021
PS1061-C-001
PS1061-C-002
PS1061-C-003
PS1061-C-004
PS1061-C-005
Technical Description of Components1. CompressorThis is a fully hermetic, high back pressure single phase type; the internal components being mounted
Technical Data TableModelC9-1C14-1C19-1C31-2C39-2C58-2Nominal Airflow †m3/min0.580.831.161.832.333.5Nominal Pressure Dropbar0.30.30.30.30.30.3Maximum
Technical Data TableModelC92-3C120-3C147-3C175-4C238-4Nominal Airflow †m3/min5.57.168.8310.514.33Nominal Pressure Dropbar0.30.30.30.30.3Maximum Workin
ContentsDescriptionPageIntroduction3Warranty3Health and Safety4Machine Card4General Safety Instructions5Refrigerant R134a Safety Data6Installation8Ins
Electrical DescriptionDescription of Components1."ON / OFF" SwitchThis switches the live side of the power supply to the circuit. All models
Wiring DiagramsTo assist understanding of the electrical circuitry the following wiring diagrams are included:Model NumbersSchematic WiringDiagram Num
PS1061-C-011
PS1061-C-012
PS1061-C-013
PS1061-C-014
Control of Refrigerant DischargeBy international agreement, the worldwide use of certain refrigerants will be reduced in stages. To this end,listed b
Routine MaintenanceIt is not normally necessary to open the refrigerant circuit. If a problem is suspected it is strongly recommendedthat unit mainte
Fault FindingThe following fault finding chart relates various symptoms and faults of the refrigeration system.Before attempting to identify a refrige
Fault Finding continuedPROBLEMCAUSESYMPTOMREMEDY Compressed air flow rate toohigh. Pressure downstream fromthe dryer lower than theexpected value. Red
ImportantThe refrigerant available on the C series of Compressed Air Dryers is Refrigerant R134a or RefrigerantR407C. It is imperative that refrigeran
Fault Finding continuedPROBLEMCAUSESYMPTOMREMEDY Fan motor stop working Every LED at electronicscontrol board doesn’t light soits similar to no electr
Notes
Denco Limited - General InformationDenco LimitedHead OfficeDolphin House, Moreton Business Park,Moreton-on-Lugg, Hereford, HR4 8DS, UK.Telephone: +44
Health and SafetyDue regard shall be given to observing safe procedures when working with or on the equipment. It is theresponsibility of the Install
General Safety InstructionsIMPORTANT:THE FOLLOWING SAFETY PRECAUTIONS MUST BE READ AND UNDERSTOOD BEFOREREPAIR OR MAINTENANCE WORK IS ATTEMPTED.Genera
Refrigerant Safety DataReactivity DataUnstableStabilityStableYESConditions to AvoidUse in presence of naked flames, red-hot surfaces. High moisture le
Health Hazard Data and First AidShort term effects of over exposure when:In contact with skin: Liquid splashes may cause freeze burns. No information
Installation - GeneralStorageThe equipment should be stored in a secure frost free area with a maximum ambient of 55°C and maximumhumidity of 90% non-
Installation - ElectricalThe C series Dryers require a 220/240 Volt 1 phase and neutral 50-60 Hz supply. A flying lead is installed on thedryer for co